  • Product Name:HD-8 Series 10kV,35kV Cross-linked Cable Indoor And Outdoor Termination And Intermediate Connection
Products Proinfo
The thermal shdnkable cable accessory uses three seals and two earthings,which is strongly recommended by cable network expels.

Product specification


1. The cross-linked cable thermal shrinkable termination uses the double-earthing technology,in which the steel armour earthing separates from the copper shield earthing so that the cable trial is more reasonable.
A. Test the steel armour earthing and each resistance,if it is conducted,it means the cable protection surface is dameged.
B. Test the resistance between two earthings,if it is conducted,it means the external sheath is damaged; test the eadh resistance of copper shield earthing,if it is conducted,it means both the intemal and extemal protection sufaces are damaged.
C. The phase will never fade.
D. The triangular pdck is developed for the purposeof convenient operation.
E. The taper-shaped fingertip will never be cracked.
2. The cross-linked cable thermal shrinkable intermediary connection uses the new technology(three-seal technology)
A. The breakdown of cable intermediary jctnt is caused by poor seal,so our company adopts the new technology to make the cable operate more sefely and conveniently. The three-seal refers to the external protection seal Internal protection seal, and the seal between two ends of insulation tube.
B. The insulation tube is prolonged to solve the problem of power seize.
C. The protection tube is very soft and flame retardant

Fittings of 10kV outdoorthermal shrinkable cable
1、Three-conductor fingertip
2、Thermal shdnkable ring
3、Single-aperture skirt
4、Earthing
5、Silicone grease
6、Stress evacuation Daster
7、Fill,sealant
8、Prick
9、Sealtube
10、Insulation tube
11、Three-aperture skirt
12、Stress coatml tube
13、Phase ring
14、Fittings

Structure of 10kV three-conductor termination


Single-phase dissection diagram


10kV Cross-linked cable intermediate connection single-phase structure
1.Conductor 10.Shield tube
2.Internal semi-conducting surface 11.Semi-conducting strip
3.XLPE insulation 12.Fill
4.External semi-conducting surface 13.Stress evacuation paster
5.Copper shield 14.Sealant
6.Connection tube 15.Copper shield net
7.Stress control tube 16.Copper weaving net
8.Internal insulation tube 17.Band
9.External insulation tube  

10kV Indoor and outdoor termination and Intermediate connection
Test Item Standard requirement Result Conclusion
Power-frequency
voltage resistance test
45kV,1min non-flash, non-breakdown 45kV,1min non-flash,
non-breakdown
Pass
Partial power discharge test Power discharge ≤20PC under 13kV Power discharge
≤20PC under 13kV
Pass
Load cycle test Heating to 95~100℃ ,cycling for 5h
heating 3h and cooling 3h,3 cycles
3 cycles when heating
to 95~100℃
Assessed from the tests below
Partial power discharge test Power discharge ≤20PC under 13kV Power discharge
≤20PC under 13kV
Pass
Impulse voltage test 105kV,10times for both positive and
negative pole , non-flash , non-breakdown
105kV,10times for both
positive and negative pole ,
non-flash , non-breakdown
Pass
Negative pole DC voltage 52kV,15min non-flash , non-breakdown 52kV,15min non-flash ,
non-breakdown
Pass
Power-frequency
voltage resistance test
35kV,4h non-flash , non-breakdown 35kV,4h non-flash ,
non-breakdown
Pass

Model Name Application cable
section (mm2)
10kV HRYN-1/1 10kV cross-linked cable thermal shrinkable
indoor termination (single-conductor)
25~50
10kV HRYN-1/2 70~120
10kV HRYN-1/3 150~240
10kV HRYW-1/1 10kV cross-linked cable thermal shrinkable
outdoor termination (single-conductor)
25~50
10kV HRYW-1/2 70~120
10kV HRYW-1/3 150~240
10kV HRYN-3/1 10kV cross-linked cable thermal shrinkable
indoor termination (three-conductor)
25~50
10kV HRYN-3/2 70~120
10kV HRYN-3/3 150~240
10kV HRYW-3/1 10kV cross-linked cable thermal shrinkable
outdoor termination (three-conductor)
25~50
10kV HRYW-3/2 70~120
10kV HRYW-3/3 150~240
10kV HRYJ-3/1 10kV cross-linked cable thermal shrinkable
intermediary connection (three-conductor)
25~50
10kV HRYJ-3/2 70~120
10kV HRYJ-3/3 150~240
10kV HRZN-3/1 10kV cross-linked oil impregnated cable
indoor and termination (three-conductor)
25~50
10kV HRZN-3/2 70~120
10kV HRZN-3/3 150~240
10kV HRZW-3/1 10kV cross-linked oil impregnated cable
outdoor and termination (three-conductor)
25~50
10kV HRZW-3/2 70~120
10kV HRZW-3/3 150~240
10kV HRZJ-3/1 10kV cross-linked oil impregnated cable
intermediary termination (three-conductor)
25~50
10kV HRZJ-3/2 70~120
10kV HRZJ-3/3 150~240
35kV HRYN-3/1 35kV cross-linked cable thermal shrinkable
indoor termination (three-conductor)
25~50
35kV HRYN-3/2 70~120
35kV HRYN-3/3 150~240
35kV HRYW-3/1 35kV cross-linked cable thermal shrinkable
outdoor termination (three-conductor)
25~50
35kV HRYW-3/2 70~120
35kV HRYW-3/3 150~240
35kV HRYN-1/1 35kV cross-linked cable thermal shrinkable
indoor termination (single-conductor)
25~50
35kV HRYN-1/2 70~120
35kV HRYN-1/3 150~240
35kV HRYW-1/1 35kV cross-linked cable thermal shrinkable
outdoor termination (single-conductor)
25~50
35kV HRYW-1/2 70~120
35kV HRYW-1/3 150~240